Elkay ECDFPW Manuale Utente

Navigare online o scaricare Manuale Utente per no Elkay ECDFPW. Elkay ECDFPW User's Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 4
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
97749C (Rev. J - 7/07)
ECDFPW314C ECDFPWVR314C
Installation/Care/Use Manual
Soft Sides
Fountains with FLEXI-GUARD
®
To assure you install this model easily and correctly,
PLEASE READ THESE SIMPLE INSTRUCTIONS BEFORE STARTING THE
INSTALLATION. CHECK YOUR INSTALLATION FOR COMPLIANCE WITH
PLUMBING, ELECTRICAL AND OTHER APPLICABLE CODES. After installation, leave
these instructions inside the fountain for future reference.
IMPORTANT! INSTALLER PLEASE NOTE.
THE GROUNDING OF ELECTRICAL EQUIPMENT SUCH AS TELEPHONE, COMPUTERS, ETC. TO
WATER LINES IS A COMMON PROCEDURE. THIS GROUNDING MAY BE IN THE BUILDING OR MAY
OCCUR AWAY FROM THE BUILDING. THIS GROUNDING CAN CAUSE ELECTRICAL FEEDBACK
INTO A FOUNTAIN, CREATING AN ELECTROLYSIS WHICH CAUSES A METALLIC TASTE OR AN
INCREASE IN THE METAL CONTENT OF THE WATER. THIS CONDITION IS AVOIDABLE BY USING
THE PROPER MATERIALS AS INDICATED. ANY DRAIN FITTINGS PROVIDED BY THE INSTALLER
SHOULD BE MADE OF PLASTIC TO ELECTRICALLY ISOLATE THE FOUNTAIN FROM THE BUILDING
PLUMBING SYSTEM.
IMPORTANT
ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SERVICE PERSON
FIG. 2FIG. 1
ECDFPW314C
Installer
NOTE: WATER FLOW
DIRECTION
BUILDING WATER
INLET
SERVICE STOP
(NOT FURNISHED)
1/4" O.D. TUBE
WATER INLET
TO COOLER
3/8" O.D. UNPLATED
COPPER TUBE CONNECT
COLD WATER SUPPLY
Vedere la pagina 0
1 2 3 4

Sommario

Pagina 1 - Installation/Care/Use Manual

97749C (Rev. J - 7/07)ECDFPW314C ECDFPWVR314CInstallation/Care/Use ManualSoft Sides™ Fountains with FLEXI-GUARD®To assure you install this model e

Pagina 2 - ECDFPW314C

97749C (Rev. J - 7/07)ECDFPW314C ECDFPWVR314CFIG. 3PAGE 2LEGENDA = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT S

Pagina 3 - 97749C (Rev. J - 7/07)

97749C (Rev. J - 7/07)ECDFPW314C ECDFPWVR314CPAGE 3INSTALLATION INSTRUCTIONS1. Wall should already be framed for the fountain using the positioni

Pagina 4

97749C (Rev. J - 7/07)ECDFPW314C ECDFPWVR314CPAGE 4FOR PARTS, CONTACT YOUR LOCAL DISTRIBUTOR OR CALL 1.800.323.0620ELKAY MANUFACTURING COMPANY • 2

Commenti su questo manuale

Nessun commento